. 2024 Oct 10;206(11):430.
doi: 10.1007/s00203-024-04154-6.

Active-bromide and surfactant synergy for enhanced microfouling control

Affiliations

Active-bromide and surfactant synergy for enhanced microfouling control

Sudhir K Shukla et al. Arch Microbiol. .

Abstract

Biofilms are structured microbial communities encased in a matrix of self-produced extracellular polymeric substance (EPS) and pose significant challenges in various industrial cooling systems. A nuclear power plant uses a biocide active-bromide for control of biological growth in its condenser cooling system. This study is aimed at evaluating the anti-bacterial and anti-biofilm efficacy of active-bromide against planktonic and biofilm-forming bacteria that are commonly encountered in seawater cooling systems. The results demonstrated that active-bromide at the concentration used at the power plant (1 ppm) exhibited minimal killing activity against Pseudomonas aeruginosa planktonic cells. The bacterial cell surface hydrophobicity assay using Staphylococcus aureus and P. aeruginosa indicated that Triton-X 100 significantly decreased the hydrophobicity of planktonic cells, enhancing the susceptibility of the cells to active-bromide. Biofilm inhibition assays revealed limited efficacy of active-bromide at 1 ppm concentration, but significant inhibition at 5 ppm and 10 ppm. However, the addition of a surfactant, Triton-X 100, in combination with 1 ppm active-bromide displayed a synergistic effect, leading to significant biofilm dispersal of pre-formed P. aeruginosa biofilms. This observation was substantiated by epifluorescence microscopy using a live/dead bacterial assay that showed the combination treatment resulted in extensive cell death within the biofilm, as indicated by a marked increase in red fluorescence, compared to treatments with either agent alone. These findings suggest that active bromide alone may be insufficient for microfouling control in the seawater-based condenser cooling system of the power plant. Including a biocompatible surfactant that disrupts established biofilms (microfouling) can significantly improve the efficacy of active bromide treatment.

Keywords: Active-bromide; Antibacterial activity; Biofilm; Biofouling control; Condenser cooling system; Surfactant dispersal.

PubMed Disclaimer

Similar articles

References

    1. Banat IM, De Rienzo MA, Quinn GA (2014) Microbial biofilms: biosurfactants as antibiofilm agents. Appl Microbiol Biotechnol 98(24):9915–9929 - DOI - PubMed
    1. Boyce, J. M. (2023). Quaternary ammonium disinfectants and antiseptics: tolerance, resistance and potential impact on antibiotic resistance. Antimicrobial Resistance & Infection Control, 12(1), 32.
    1. Cai M, Liu W, Sun W (2018) Formation and speciation of disinfection byproducts in desalinated seawater blended with treated drinking water during chlorination. Desalin Water Treat 437:7–14 - DOI
    1. Ceresa C et al (2020) The effect of sophorolipids against microbial biofilms on medical-grade silicone. J Biotechnol 309:34–43 - DOI - PubMed
    1. Codony F, Morato J, Mas J (2005) Role of discontinuous chlorination on microbial production by drinking water biofilms. Water Res 39(9):1896–1906 - DOI - PubMed

MeSH terms

LinkOut - more resources